Characteristics |
2200 |
3000 - 3000 XL |
Rating |
2200 VA / 1980 W |
3000 VA / 2700 W(1) |
Format |
RT2U (tower / rack 2U) and RT3U (tower / rack 3U) |
Electrical characteristics |
Architecture |
On-line double conversion with automatic by-pass and power factor correction |
Input voltage and frequency ranges without using batteries |
100/120/160/184 V(3) to 284V - 40 to 70 Hz |
Output voltage and frequency |
230V (adjustable to 200/208/220/240 V), 50/60 Hz auto-select or frequency converter mode |
Connections |
Inputs |
1 IEC C20 (16A) or terminal block on HotSwap MBP HW (Hard-Wired) |
Outputs |
8 IEC C13 (10A) sockets + 1 IEC C19 (16A) socket on Pulsar M |
Remotely controlled Powershare sockets |
2 groups of 2 x IEC C13 (10A) on Pulsar M |
Additional outputs with HotSwap MBP FR/DIN/BS/IEC/HW |
4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10A sockets or terminal blocks (HW version) |
Additional outputs with HotSwap MBP FR/DIN/BS/IEC/HW |
4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10A sockets or terminal blocks (HW version) |
Additional outputs with FlexPDU FR/DIN/BS/IEC |
8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10A sockets |
Batteries Typical backup times for 50 and 70% of the VA rating except for Pulsar M 3000XL(4) |
Pulsar M |
17 mn / 12 mn |
15 mn / 10 mn |
Pulsar M+ 1 EXB |
85 mn / 60 mn |
60 mn / 40 mn |
Pulsar M + 4 EXB |
285 mn / 200 mn |
190 mn / 150 mn |
Battery management |
Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition of external battery units => continuous maximisation of backup time + deep discharge protection |
Interfaces |
Indicators and display |
3 LEDs + adjustable multilingual display: display of measurements, access to control and set-up menus |
Communication ports |
1 USB port + 1 RS232 serial port(5) + 1 mini terminal block for remote ON/OFF and emergency stop |
Communications card slots |
1 slot for
NMC Minislot 2006 card (included in Netpack version) or NMC ModBus/JBus or
MC Contacts/Serial |
Operating conditions, standards and approvals |
Operating temperature noise level |
0°C to 40°C continuous, 45 dBA |
Performance - Safety - EMC |
IEC/EN 62 040-3, IEC/EN 62040-1-1, IEC/EN 60950-1 (RD), IEC/EN 62 040-2 C1 Class |
Approvals |
CE, TüV GS, CB report, UL 1778 cUL CSA 22.2 |
Dimensions (H x W x D) / Weight |
Pulsar M RT (3U) |
131 x 440 x 490 mm (compatible with 600 mm deep rack) / 30 kg |
131 x 440 x 490 mm (compatible with 600 mm deep rack) / 30 kg (3000 XL = 18 kg) |
Pulsar M RT2U |
86 x 440 x 640 mm / 31 kg |
Pulsar M EXB RT3U |